Certified Single-Level Reformulation for Tri-Level Cyber-Physical Grid Security
Debraj Banerjee ⋅ Gurunath Gurrala ⋅ Kunal Narayan Chaudhury
Abstract
Modern power grids are increasingly exposed to coordinated cyber-physical disruptions, where the outage of a small number of transmission components can trigger severe post-contingency load shedding. Designing proactive *security defense* against such adversarial contingencies is naturally modeled as a tri-level Defender-Attacker-Operator (DAO) problem: the defender allocates limited hardening resources, the attacker selects worst-case line outages, and the operator solves a post-attack DC/AC-optimal power flow (OPF). However, the resulting tri-level program is computationally prohibitive even for moderate network sizes. We develop a certified four-step reformulation pipeline that converts this intractable tri-level DAO problem into a tractable single-level optimization, yielding a Single-Level Mixed-Integer Linear Program (SL-MILP) under DC-OPF and a Single-Level Mixed-Integer Conic Program (SL-MICP) under a convex SOCP relaxation of AC-OPF. The construction is exact except for one controlled relaxation of the attacker's binary decisions. It provides two complementary guarantees: the single-level value $S_{\mathrm{SL}}$ is an a-priori conservative bound, while one post-hoc binary attacker-operator solve at the returned defense gives the exact realized certificate $S_{\mathrm{true}}(d^*_{\mathrm{SL}})\le S_{\mathrm{SL}}$. Experiments on IEEE power systems up to 118 buses for DC and 57 buses for AC quantify both certificate gaps and runtime while demonstrating substantial computational gains.
Successful Page Load